.1 This Clause contains a comprehensive range of field devices listed alphabetically by ``Point type'' code, not
all of which will necessarily be applicable to this project. Refer to the ``Point Type'' column on the points lists
in Section 15930 to identify the devices relevant to this project.2 Some point types have a number as the last character in order to identify variations in a group of similar field
devices. For each separate point type or group of similar devices (common point type except for number) all
items provided shall be the product of one manufacturer..3 All field devices shall be selected to have full compatibility with the SAPs, TUCs or other controls
components being proposed..4 Any field device proposed for use which is not one of the products listed under ``Standard of Acceptance''
will be evaluated by the Owner's representative against the specified technical performance and the quality
and characteristics of the products which are listed. If any proposed field device is deemed not equivalent to
the specification, then the Contractor shall provide another device which does meet specification at no cost..5 The proposal must include technical data for all field devices listed in the points lists, specifically
cross-referenced to the particular point type to facilitate an unambiguous proposal evaluation..6 Some devices may require different ranges, capacities, etc. in particular applications, even though the device
or component is otherwise the same. Where definition of such variations is required in the specifications or
points lists, the point type will use suffixes, for example ``DPS/x'' or ``DA1/x''. The suffixes are explained in
the ``Technical Performance'' portion of each point type specification.
.7 The end-to-end accuracy required for analog devices shall include the combined effect of sensitivity,
hysteresis, linearity and repeatability between the measured variable and the output at the operator interface
device, or between the panel signal to the digital-to-analog converter and the controlled variable..8 Devices shall meet the specific requirements listed, and shall be compatible with respect to power supply,
signal characteristics, or other factors with the CCS being proposed. Power supplies shall be provided as
required for any and all devices.
.1 Description - Control Relay Status ``CRS'' is used where the field device will be either:
- an auxiliary dry contact, supplied as part of the equipment whose status will be monitored by this
point, or- if there is no auxiliary dry contact on the equipment, a relay as specified in 2. and 3., provided by the
control contractor..2 Technical Performance - a high impedance relay to produce a dry contact.
.3 Standard of Acceptance - Omron Model GSD
- Veris Model 607 voltage bug.
.1 Description - Control Relay (Solid State)
.2 Technical Performance - 240 V, 10 amp capacity, SPST function. Normally open (or normally closed) as
required by points list or application complete with optical isolation. Suitable for switching inductive AC
loads..3 Standard of Acceptance - Electromatic - RS104240
- Potter & Brumfield EOTZ Series
- Grayhill 7052-04-C-12-S.
.1 Description - Control relay (dry contact electro-mechanical relay).
.2 Technical Performance - 240 V, 10A to suit application.
.3 Standard of Acceptance - IDEC-RH Series
- Johnson R1020 series.
.1 Description - Control relay (Solid state relay suitable for switching D.C. loads).
.2 Technical Performance - 60 VDC.
.3 Standard of Acceptance - Grayhill.
6.7 Point Type ``CS2''.1 Description - Current sensor (analogue).
.2 Technical Performance - Self powered, with insertion impedance loss less than 0.0006 ohms under all
conditions. End-to-end accuracy +/- 2% of full scale at each range. Ranges: 1.0 to 10.0 amps, low;
5 to 50 amps, middle; 20 to 200 amps, high; selectable by switch or by setting jumpers..3 Standard of Acceptance - Greystone CS-150.
6.8 Point Type ``CV1''.1 Description - Current Sensor (switch).
.2 Technical Performance - Solid State N.O. AC switch. Same ranges as point type ``CS1''. Manual
adjustment of switch threshold setting..3 Standard of Acceptance - Greystone CS-125.
.1 Description - Control Valve (2 way, 2 position)
.2 Technical Performance - Brass or bronze globe valve construction, with screwed ends. Materials suitable
for chilled water or hot water up to 125 deg C. 24 VAC. Working pressure, 875 kPa. N.O. spring return.
Minimum close off pressure rating shall meet requirements in the points lists; if no requirement, minimum
close off pressure rating shall be 70 kPa..3 Standard of Acceptance - Honeywell V8043 series
- Johnson J-series
6.10 Point Type ``CV3''.1 Description - Control Valve (2 way, floating control).
.2 Technical Performance - Brass or bronze body, globe valve with equal percentage flow characteristic,
screwed ends. Materials suitable for chilled water or hot water up to 125 deg C. Working pressure 875
kPa 24 VAC reversing motor drive. Minimum close off pressure rating shall be 30 psi, or as stated in the
points list, which ever is higher..3 Standard of Acceptance - Johnson
- Honeywell.4 Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv
is specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to
that specified.
6.11 Point Type ``CV4''.1 Description - Control Valve (2 way modulating, non-spring-return).
.2 Technical Performance - Globe valve body, with equal percentage flow characteristics. Materials suitable for
chilled water or hot water up to 125 deg C. Modulating actuator with 0-10 VDC signal range, power to
open and power to close. Working pressure 875 kPa..3 Standard of Acceptance - Johnson
- Honeywell.4 Submittal Data - Submittal data shall include the proposed Cv rating for each control valve. If a specific Cv
is specified in the points list or on a valve schedule, ensure the control valve proposed has a similar Cv to
that specified.
6.10.2..1 Description - Control Valve (2 way, modulating, spring return).
.2 Technical Performance - Technical performance shall be as specified in
.3 Standard of Acceptance -
Johnson
- Honeywell
.4 Submittal Data - Submittal data shall include the proposed Cv
rating for each control valve. If a specific Cv
is specified in the points list or on a valve
schedule, ensure the control valve proposed has a similar Cv to
that specified.
.1 Description - Damper Actuator (Electric, modulating, non-spring-return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC.
- Control Voltage 0 - 10 VDC.Suffixes - ``DA1/A'' - 50 in-lb torque capacity.
- ``DA1/B'' - 90 in-lb torque capacity.
- ``DA1/C'' - 130 in-lb torque capacity.
6.14 Point Type ``DA3/x''.1 Description - Damper Actuator (Electric, modulating, spring return).
.2 Technical Performance - Power voltage 24 VAC or 120 VAC
- Control Voltage 0 - 10 VDCSuffixes - ``DA2/A" - 50 in-lb torque capacity.
- ``DA2/B'' - 90 in-lb torque capacity.
- ``DA2/C'' - 133 in-lb torque capacity..3 Standard of Acceptance - Belimo FM-24SR, NF-24 SR (``DA2/A'')
- Belimo AF-24SR, (``DA2/C'')
- Johnson Controls M130-GGA (``DA2/A'' only)
6.15 Point Type ``DA4/x''.1 Description - Damper Actuator (Electric, 2-position, non-spring-return).
.2 Technical Performance - Power Voltage 24 VAC or 120 VAC
Suffixes - ``DA3/A'' - 50 in-lb torque capacity.
- ``DA3/B'' - 90 in-lb torque capacity.
- ``DA3/C'' - 130 in-lb torque capacity..3 Standard of Acceptance - Belimo NM-24 (``DA3/A'')
- Belimo SMC-24 (``DA3/B'')
- Belimo SM-24 (``DA3/C4/'')
.1 Description - Damper Actuator (Electric, 2-position, spring return).
.2 Technical Performance - Power Voltage, 24 VAC or 120 VAC.
Suffixes - ``DA4/A'' - 130 in-lb.
.3 Standard of Acceptance - Belimo SF-24.
- Belimo SF-120.
.1 Description - Point type ``DDC'' is used to describe on analog output which is to be connected to a piece of
equipment not supplied by the controls contractor for the purpose of controlling that equipment's operation in
some way. Examples would be an output to a variable speed drive to control its speed, or an output to a
modulating chiller (or boiler) to control its operating output.
.2 The controls contractor shall provide wiring, and interface devices.
.1 Description - Duct mounted relative humidity sensor.
.3 - Standard of Acceptance - Greystone HS-250-C-02
- Hy-cal CT-829-A
6.19 Point Type ``DTS1/x''.2 Technical Performance - Solid-state design, operating on capacitance principle, with non-interactive fine
resolution, zero, and span adjustments. End-to-end accuracy +/- 2% of full scale pressure range, including
temperature compensation. Shall have integral filters at each air connection port.Suffixes - ``DPS/A'' - 0 to 25 PA pressure range.
- ``DPS/B'' - 0 to 50 PA pressure range.
- ``DPS/C'' - 0 to 75 PA pressure range.
- ``DPS/D'' - 0 to 125 PA pressure range.
- ``DPS/E'' - 0 to 250 PA pressure range.
 bsp; - ``DPS/F'' - 0 to 500 PA pressure range.
- ``DPS/G'' - 0 to 750 PA pressure range.
- ``DPS/H'' - 0 to 1250 PA pressure range..3 Standard of Acceptance - Modus T20-xxx, T30-xxx, or T40-xxx
to suit pressure range and application.
- Autotran 700.
6.20 Point Type ``DTS2''.1 Description - Duct temperature sensor, with an averaging element.
.2 Technical Performance - Constructed of FT6 plenum rated cable or soft copper tubing, incorporating
0.3 deg C. Assembly complete with wiring housing and
numerous temperature sensors encapsulated at equal distances along the length of the element. The assembly
acts as a single sensor, reporting the average temperature from all the individual sensors. Operating range: 0
deg C to 60 deg C; end-to-end accuracy +/-
mounting flange.Suffixes - ``DTS1/A'' -
3.5 m sensor cable length
- ``DTS1/B'' - 6.0 m cable length.3 Standard of Acceptance - Greystone TE-200
- Pre-con
6.21 Point Type ``FRZ''.1 Description - Duct temperature sensor, with probe type element.
.2 Technical Performance - Sensor encapsulated in a 200 mm long, 6 mm OD copper or stainless steel probe.
0.3 deg C. Assembly complete with wiring
Operating range 0 deg C to 60 deg C; end-to-end accuracy +/-
housing and mounting flange..3 Standard of Acceptance - Greystone TE-200-B-7-C
- Pre-con
6.22 Point Type ``GAS1''.1 Description - ``Freezestat'' auto-reset, complete with auxiliary dry contact in order to provide a separate
digital input to the DDC system..2 Technical Performance - Range: -10 deg C to 15 deg C; probe length 6 m. Control responds to the lowest
0.3 m of the entire length of the element.
temperature along any.3 Standard of Acceptance - Penn A170-GA-1
6.23 Point Type ``GAS2''.1 Description - CO2 concentration sensor.
.2 Technical Performance - 0 - 2500 ppm +/- 2% Full Scale.
.3 Standard of Acceptance - Quatrosense Environmental Ltd. QEL QTS - 2000.
6.24 Point Type ``GAS3''.1 Description - Carbon monoxide concentration sensor.
.2 Technical Performance - 0 - 125 ppm CO output drift < 2% signal/month.
.3 Standard of Acceptance - Quatrosense Environmental Ltd.
.1 Description - flammable gas concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.25 Point Type ``GAS4''6.26 Point Type ``GAS5''.1 Description - Refrigerant vapour concentration sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
6.27 Point Type ``LS1''.1 Description - Total volatile organic compounds (TVOC's) concentration sensor, designed for mounting
within an occupied space. This type of device is sometimes referred to as an indoor air quality sensor..2 Technical Performance -
.3 Standard of Acceptance -
1.5 K ohm..1 Description - Photocell light level sensor, with analogue output related to light intensity.
.2 Technical Performance - Dark 1 meg ohm, bright
.3 Standard of Acceptance - Greystone PSR-1.
6.28 Point Type ``LS2''6.29 Point Type ``OS1''.1 Description - Photocell, adjustable light level switch.
.2 Technical Performance -
.3 Standard of Acceptance -
6.30 Point Type ``OTS''.1 Description - Passive infrared occupancy sensor.
.2 Technical Performance -
.3 Standard of Acceptance -
0.3 deg C over the entire operating range..1 Description - Outside air temperature sensor.
.2 Technical Performance - 10 K ohm thermistor sensor encapsulated in a 6 mm OD probe, complete with
weatherproof enclosure, sun shield and mounting bracket. Operating range: -35 deg C to +50 deg C.
End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-F, c/w 100 K ohm parallel resistor.
6.31 Point Type ``PS1''.1 Description - Pipe Pressure Transducer.
.2 Technical Performance - Brazed assembly with 300 series stainless steel parts that are in contact with the
media, snap tract and circuit board c/w external pressure sensor and mounted in a NEMA 4 enclosure.
Accuracy +/- 0.3% span from best fit straight line.
.3 Standard of Acceptance - Greystone PGS-100
6.32 Point Type ``PTS1''.1 Description - Pipe Temperature Sensor, immersion type .
0.3 deg C over the entire.2 Technical Performance - 10 K ohm thermistor sensor encapsulated in a 6 mm OD, 50 mm long probe, with
screw fitting for insertion into a standard thermowell. Sensor assembly to be complete with enclosure and
thermowell. Operating range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-C
6.33 Point Type ``PTS2''0.3 deg C over the entire.1 Description - Pipe Temperature Sensor, strap-on type.
.2 Technical Performance - 10 K ohm thermistor encapulated in a stainless steel pad designed for strap-on
installation. Assembly to be complete with solid-state circuitry in an enclosure and connecting cable to the
thermistor. Operating range: -10 deg C to 100 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-E-7
6.34 - Point Type ``RHS''3.0% of operating range, with maximum temperature dependence of 0.2%.1 Description - Relative Humidity Sensor Room Type.
.2 Technical Performance - operating range: 10% RH to 90% RH, over a 0 deg C to 60 deg C temperature
range. End-to-end accuracy: +/-
.3 Standard of Acceptance -
Greystone HS-150-B-02
- Hy-cal C102-H
0.3 deg C over the entire operating range..1 Description - Room temperature sensor complete with momentary override switch.
.2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted on a
circuit board/baseplate for wall mounting, complete with a vented, plastic enclosure. Operating range: 10 deg
C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-AE-OR
6.36 Point Type ``RTS2''0.3.1 Description - Room Temperature Sensor, security type.
.2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted on a
rigid, metal cover plate designed for mounting into a recessed junction box. The sensing element shall be
attached directly to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance - Greystone TE-200-AS
6.37 Point Type ``RTS3''0.3.1 Description - Room temperature sensor complete with momentary override switch, setpoint adjustment, and
setpoint indication..2 Technical Performance - Assembly shall consist of a 10 K ohm thermistor and related circuitry mounted on a
rigid, metal cover plate designed for mounting into a recessed junction box. The sensing element shall be
attached directly to the cover plate. Operating range: 10 deg C to 30 deg C. End-to-end accuracy: +/-
.3 Standard of Acceptance
- Greystone TE-200-IT
- Delta Intellistat RTS406
6.39 Point Type ``VS2''.1 Description - Velocity sensor (single point flow sensor).
.2 Technical Performance - 0 - 3000 FPM Adjustable 4'' - 16'' ducts. (Thermal anemometer technology).
.3 Standard of Acceptance - BELIMO.
6.40 Point Type ``WPS''.1 Description - Air velocity sensor with thermal anemometer technology, using differential pressure signal
from a flow grid in duct or VAV box inlet..2 Technical Performance -
.3 Standard of Acceptance -
.1 Description - (Window Position Switch) Point type ``WPS'' is used to describe a digital input connected to a
dry contact which is part of a magnetic proximity switch on openable sections of glazing. The dry contact will
be open when the window is open, and closed when the window is closed..2 If the window supplier provides the proximity switches, and wiring from their dry contacts, to 300 mm above
the window head above the openable section, use the CRS designation for the point.
[